Key Considerations for Selecting Instrument Transformers

Sep 02, 2026 Leave a message

When selecting instrument transformers, various parameters must be considered, such as rated primary current/voltage, rated secondary current/voltage, accuracy class, and rated burden. Accuracy classes are typically categorized as 0.1, 0.2, 0.5, 1, 3, etc., with lower numerical values ​​indicating higher accuracy. Furthermore, installation and operation must comply with relevant standards and specifications-such as IEC and GB-to ensure safety and reliability. For instance, the secondary side of a current transformer must not be left open-circuited, as this creates a risk of high voltage; conversely, the secondary side of a voltage transformer must not be short-circuited, as this can cause equipment damage.

‌Rated Voltage and Current‌: The rated voltage of the transformer should exceed the line's rated voltage; the primary current should be selected at 1.2 to 1.5 times the maximum load current.
‌Transformation Ratio and Secondary Current‌: Standard secondary currents are 5A or 1A; a 1A rating is recommended for long-distance transmission or high-voltage applications (330kV and above) to reduce power loss.
‌Accuracy Class‌: Select Class 0.2S or 0.5 for metering purposes, and Class 5P or 10P for protection purposes; ensure the secondary burden does not exceed the rated capacity.